DemandControlVentilation ==================================================================== Brief Description ------------------------------------------------------------------------------- Demand control ventilation verification for high-occupancy areas Index Description ------------------------------------------------------------------------------- * Section 6.4.3.8 in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * flow_volumetric_air_outdoor: Outdoor air volume flow * status_ahu: HVAC system operation status * status_economizer: Economizer status * number_occupants: Number of occupants Assertions Description ------------------------------------------------------------------------------- * i) If flow_volumetric_air_outdoor is constant over time, NO DCV presents. ii) If flow_volumetric_air_outdoor has two clusters, DCV with hbinary control presents. iii) flow_volumetric_air_outdoor is linearly correlated to status_ahu, DCV with occupant-counting based control presents Type Verification Description ------------------------------------------------------------------------------- Rule-based Assertions Type ------------------------------------------------------------------------------- Pass