ZoneTempControl ==================================================================== Brief Description ------------------------------------------------------------------------------- Zone temperature setpoint deadband >= 5f (2.77c) Detailed Description ------------------------------------------------------------------------------- Where used to control both heating and cooling, zone thermostatic controls shall be capable of and configured to provide a temperature range or dead band of at least 5°f within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. (case study for zone temperature reset, not for this one) Index Description ------------------------------------------------------------------------------- * Section 6.4.3.1.2 in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * temperature_air_zone_cool_setpoint: Zone cooling temperature setpoint * temperature_air_zone_heat_setpoint: Zone heating temperature setpoint Assertions Description ------------------------------------------------------------------------------- * temperature_air_zone_cool_setpoint - temperature_air_zone_heat_setpoint > 5F (2.77C) Type Verification Description ------------------------------------------------------------------------------- Rule-based Assertions Type ------------------------------------------------------------------------------- Pass