ZoneHeatSetpointMinimum ==================================================================== Brief Description ------------------------------------------------------------------------------- Zone heating setpoint reset temperature minimum value check Detailed Description ------------------------------------------------------------------------------- Heating systems located in climate zones 2-8 shall be equipped with controls that have the capability to automatically restart and temporarily operate the system as required to maintain zone temperatures above a heating setpoint adjustable down to 55°f or lower. (case study) Index Description ------------------------------------------------------------------------------- * Section 6.4.3.2.2 in 90.1-2004 Datapoints Description ------------------------------------------------------------------------------- * temperature_air_zone_heat_setpoint: Zone heating temperature setpoint Assertions Description ------------------------------------------------------------------------------- * if min(temperature_air_zone_heat_setpoint) <= 55°F, then pass Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass