WLHPLoopHeatRejectionControl ==================================================================== Brief Description ------------------------------------------------------------------------------- Water-loop heat pump heat rejection control Index Description ------------------------------------------------------------------------------- * Section 6.5.2.2.3 (a) in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * temperature_water_heating_max: Maximum heating loop temperature * temperature_water_cooling_min: Minimum cooling loop temperature * flow_mass_water_pump: Pump mass flow rate Assertions Description ------------------------------------------------------------------------------- * If the temperature difference between the maximum heating loop and minimum heating loop when the pump runs is greater than 11.11 °C, then pass else fail Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass