VentilationFanControl ==================================================================== Brief Description ------------------------------------------------------------------------------- Ventilation fan control Index Description ------------------------------------------------------------------------------- * Section 6.4.3.4.4 in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * number_occupants: Number of occupants * heat_sensible: Zone sensible heat load * power_fan: Fan power Assertions Description ------------------------------------------------------------------------------- * if heat_sensible = 0 and number_occupants = 0 and power_fan != 0 then fail else pass Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass