InteriorLightingControlAutomaticFullOff ==================================================================== Brief Description ------------------------------------------------------------------------------- Interior lighting control automatic full off Datapoints Description ------------------------------------------------------------------------------- * number_occupants: Number of occupants * power_light_total: Total lighting power * area_lit: Lit floor area Assertions Description ------------------------------------------------------------------------------- * The algorithm verifies that the device/system doesn't serves more than 5,000 ft2 and that if it doesn't, if occupants are not present for at least 20 minutes, the lighting power of the device/system should be less or equal to 0.02 W/ft2, otherwise, the verification fails. Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass