HeatPumpSupplementalHeatLockout ==================================================================== Brief Description ------------------------------------------------------------------------------- Supplemental heating coil should be off when the heat pump can meet the load by itself Index Description ------------------------------------------------------------------------------- * Section 6.4.3.5 Heat Pump Auxiliary Heat Control and 6.3.2.h Criteria in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * capacity_full_load: Heating Coil Reference Capacity * load_operation: Heating Coil Runtime Fraction * capacity_modifier_temperature: Heating Coil Heating Rate * power_heating_supplemental: Supplemental Heating Rate * capacity_modifier_fraction_flow: Heating Capacity Function of Flow Fraction Curve * load_defrost: Defrost load on the heating coil Assertions Description ------------------------------------------------------------------------------- * If capacity_full_load * capacity_modifier_temperature >= load_operation and power_heating_supplemental == 0 then pass else fail Type Verification Description ------------------------------------------------------------------------------- Rule-based Assertions Type ------------------------------------------------------------------------------- Pass