G36TerminalBoxVAVDamperTracking ==================================================================== Brief Description ------------------------------------------------------------------------------- Terminal box airflow control with vav damper following the guideline 36 recommendations Index Description ------------------------------------------------------------------------------- * Section 5.5.5.4 in ASHRAE Guideline 36-2021 Datapoints Description ------------------------------------------------------------------------------- * command_damper_vav: VAV damper command * flow_volumetric_air_discharge: Discharge airflow rate * flow_volumetric_air_setpoint: Airflow setpoint Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass Assertions Description ------------------------------------------------------------------------------- * if abs(flow_volumetric_air_setpoint - flow_volumetric_air_discharge) >= 0 (less than 1hr): * pass * elif abs(flow_volumetric_air_setpoint - flow_volumetric_air_discharge) < 0: * pass * if flow_volumetric_air_discharge - flow_volumetric_air_setpoint >= 0 (continously) and command_damper_vav <= 1: * pass * elif flow_volumetric_air_setpoint - flow_volumetric_air_discharge >= 0 (continuously) and command_damper_vav >= 99: * pass * else: * fail * end