G36FreezeProtectionStage2 ==================================================================== Brief Description ------------------------------------------------------------------------------- G36 freeze protection stage 2 requirements Index Description ------------------------------------------------------------------------------- * Section 5.16.12.2. in Guideline 36-2021 Datapoints Description ------------------------------------------------------------------------------- * temperature_air_supply_setpoint: Supply air temperature * position_damper_air_outdoor: Outdoor air damper position Assertions Description ------------------------------------------------------------------------------- * if temperature_air_supply_setpoint < 3.3 (continuously 5 minutes) and position_damper_air_outdoor > 0 (ever in the following hour): * fail * else: * pass * if never (temperature_air_supply_setpoint < 3.3 (continuously 5 minutes)): * untested Type Verification Description ------------------------------------------------------------------------------- Rule-based Assertions Type ------------------------------------------------------------------------------- Pass