Electric Equipment

Introduction

The userdata_electric_equipment.csv contains compliance data for electric equipment compliance calculations that includes receptacles and process loads including motors, elevators and refrigeration equipment loads.

It consists of the following fields:

For example, consider 2 elevators for 3 stories in a building. One of the line items in the .csv would be put in as follows:

name fraction_of_controlled_receptacles receptacle_power_savings motor_horsepower motor_efficiency motor_is_exempt elevator_weight_of_car elevator_rated_load
2 Elevator Lift Motors 1999 0.72 false 1000 900
elevator_counter_weight_of_car elevator_speed_of_car elevator_number_of_stories elevator_number_of_lifts elevator_area_ft2 elevator_ventilation_cfm refrigeration_equipment_class
1200 200 3 2 25 1000
refrigeration_equipment_volume refrigeration_equipment_total_display_area
0 0

Line items for receptacles and refrigeration equipments can also be added in the same .csv in a similar manner.

Data Fields Details

Here is a detailed explanation of what each data field requires.

name

Name of the electric equipment object in the model.

fraction_of_controlled_receptacles

This field is used to input the percentage of all controlled receptacles as a fraction. It requires a float value between 0 and 1. This value will be used to calculate the receptacle power credits according to the methodology mentioned in Table G3.1 Section 12.

receptacle_power_savings

This field is used to input the receptacle power savings directly instead of entering the fraction of controlled receptacles. One thing to remember is if both fraction_of_controlled_receptacles and receptacle_power_savings are defined in the .csv, the PRM measure will use fraction_of_controlled_receptacles.

motor_horsepower

This field is used to input the horsepower of the motor.

motor_efficiency

This field is used to input the efficiency of the motor as a percentage. It must be set up with a value from Table G3.9.1.

motor_is_exempt

Set this field to true if the motor is exempt. If it doesn’t apply, set it as false or leave empty.

elevator_weight_of_car

This field is used to input the weight of the elevator car in pounds.

elevator_rated_load

This field is used to input the proposed design elevator load at which to operate, in pounds.

elevator_counter_weight_of_car

This field is used to input the counterweight of the elevator car from Table G3.9.2, in pounds.

elevator_speed_of_car

This field is used to input the speed of the proposed elevator, in feet per minute.

elevator_number_of_stories

This field is used to input the number of stories (including basement) that is covered by the elevator.

elevator_number_of_lifts

This field is used to input the number of elevators.

elevator_area_ft2

This field is used to input the area of the elevator, in square feet.

elevator_ventilation_cfm

This field is used to input elevator ventilation fan specification, in Watt per cfm.

refrigeration_equipment_class

This field is used to input the class of the refreigeration equipment. it consists of a combination of an equipment family code, and operating mode code and a rating temperature as shown in Table G3.10.2.

refrigeration_equipment_volume

Ths field is used to input the volume of the chiller or frozen compartment, in cubic feet. Refer to Table G3.10.1.

refrigeration_equipment_total_display_area

This field is used to input the total display area of the refrigeration equipment.