The userdata_building.csv
contains compliance data for building compliance calculations. It can be used to define Appendix G HVAC systems, service water heating systems and the window to wall ratio for the entire building. The .csv consists of the following fields.
For example, consider a building named Small Office less than 5000 sqft with less than 3 floors and in climate zone 2. The entries in the userdata_building.csv file would be as follows:
name | building_type_for_hvac | building_type_for_swh | building_type_for_wwr | is_exempt_from_rotations |
---|---|---|---|---|
Small Office | other nonresidential | Office | Office <= 5,000 sq ft | false |
The resulting baseline will have a System 4 - PSZ-HP, electric resistance storage water heater and a 19% wwr.
Here is a detailed explanation of what each data field requires.
Name of the building type object in the model.
This field is used to determine the baseline model’s HVAC system. It can be overwritten at the zone level (see the documentation for userdata_thermal_zone.csv
). It should be set to one of the following values that best describes the proposed model’s building type.
heated-only storage
hospital
other nonresidential
public assembly
residential
retail
unconditioned
This field is used to determine the baseline model’s service water heating system. It should be set to one of the following values that best describes the proposed model’s building type.
All others
Automotive facility
Convenience store
Convention center
Courthouse
Dining: Bar lounge/leisure
Dining: Cafeteria/fast food
Dining: Family
Dormitory
Exercise center
Fire station
Grocery store
Gymnasium
Health-care clinic
Hospital and outpatient surgery center
Hotel
Library
Manufacturing facility
Motel
Motion picture theater
Multifamily
Museum
Office
Parking garage
Penitentiary
Performing arts theater
Police station
Post office
Religious facility
Retail
School/university
Sports arena
Town hall
Transportation
Warehouse
Workshop
This field is used to determine the baseline model’s window-to-wall ratio. It should be set to one of the following values that best described the proposed model’s building type.
All others
Grocery store
Healthcare (outpatient)
Hospital
Hotel/motel <= 75 rooms
Hotel/motel > 75 rooms
Office 5,000 to 50,000 sq ft
Office <= 5,000 sq ft
Office > 50,000 sq ft
Restaurant (full service)
Restaurant (quick service)
Retail (stand alone)
Retail (strip mall)
School (primary)
School (secondary and university)
Warehouse (nonrefrigerated)
Set this field to true if it can be demonstrated to the satisfaction of the rating authority that the building orientation is dictated by site considerations. If it doesn’t apply, leave this field blank or set to false.