Chillers

Copper can generate performance curves for all types of vapor-compression chillers. It handles two of the chiller models that are implemented in most common building energy simulation software tools; both models use performance curves that are function of the temperature of the water leaving the chiller and the part load ratio (ratio of load on the chiller to the operating chiller capacity). The main difference between the two models is that one uses performance curves that are function of the entering condenser temperature (referred to herein as the ECT model) and the other is function of the leaving condenser temperature (referred to herein as the LCT model). Additional documentation on the ECT model can be found in the EnergyPlus and DOE-2 engineering manuals; documentation on the LCT model can be found in the EnergyPlus engineering manual.

Chiller data library

The chiller library contains performance curves for existing chillers for both the ECT model and the LCT model. The number of performance curves for each compressor/condenser/model type varies; Table 1 provides a summary of the library.

Table 1 - Summary of the Chiller Library

Model

Compressor type

Condenser type

Compressor speed

Curve sets

ECT

centrifugal

air

constant

1

ECT

centrifugal

water

constant

95

ECT

centrifugal

water

variable

38

ECT

reciprocating

air

constant

1

ECT

reciprocating

water

constant

3

ECT

reciprocating

water

variable

1

ECT

screw

air

constant

9

ECT

screw

air

variable

11

ECT

screw

water

constant

38

ECT

screw

water

variable

4

ECT

scroll

air

constant

12

ECT

scroll

water

constant

7

LCT

centrifugal

air

constant

1

LCT

centrifugal

water

constant

95

LCT

centrifugal

water

variable

38

LCT

reciprocating

air

constant

1

LCT

reciprocating

water

constant

3

LCT

reciprocating

water

variable

1

LCT

screw

air

constant

9

LCT

screw

air

variable

11

LCT

screw

water

constant

38

LCT

screw

water

variable

4

LCT

scroll

air

constant

12

LCT

scroll

water

constant

7