VAVTurndownDuringReheat ==================================================================== Brief Description ------------------------------------------------------------------------------- When a vav box is in reheat mode, the ratio of v_dot_vav to v_dot_vav_max should be higher than when it isn't in reheat mode Index Description ------------------------------------------------------------------------------- * Section 6.5.2.1 ASHRAE 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * flag_coil_reheat: VAV box reheat coil operation status * flow_volumetric_air_vav: VAV airflow rate * flow_volumetric_air_max: VAV maximum airflow rate Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass Assertions Description ------------------------------------------------------------------------------- * if (flag_coil_reheat == False).all(): * Untested * else: * ratio_vav = flow_volumetric_air_vav/flow_volumetric_air_max * mean_reheat_ratio = df.loc[self.df[`flag_coil_reheat`], `ratio_vav`].mean() * mean_no_reheat_ratio = df.loc[~self.df[`flag_coil_reheat`], `ratio_vav`].mean() * if mean_reheat_ratio < mean_no_reheat_ratio: * pass * else: * fail * end