VAVMinimumTurndownDuringReheat ==================================================================== Brief Description ------------------------------------------------------------------------------- When a vav box is in reheat mode, the ratio of vav airflow rate to vav max airflow rate must not be greater than the min design turndown ratio Index Description ------------------------------------------------------------------------------- * Section 6.5.2.1 ASHRAE 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * flag_coil_reheat: VAV box reheat coil operation status * flow_volumetric_air_vav: VAV airflow rate * flow_volumetric_air_max: VAV maximum airflow rate * ratio_turndown_min: Minimum VAV turndown ratio Type Verification Description ------------------------------------------------------------------------------- Rule-based Assertions Type ------------------------------------------------------------------------------- Pass Assertions Description ------------------------------------------------------------------------------- * if flag_coil_reheat: * if flow_volumetric_air_max == 0: * Untested * if flow_volumetric_air_max > 0.0 and flow_volumetric_air_vav / flow_volumetric_air_max > ratio_turndown_min: * fail * else: * pass * else: * Untested * end