LocalLoopSaturationReverseActingMax ==================================================================== Brief Description ------------------------------------------------------------------------------- Local loop performance verification - reverse acting loop actuator maximum saturation Datapoints Description ------------------------------------------------------------------------------- * value_sensor: Feedback sensor reading * value_setpoint: Setpoint value * command_control: Control command * command_max: Maximum control command value Assertions Description ------------------------------------------------------------------------------- * If the sensed data values are consistently below its set point, and after a default of 1 hour, the control command is still not saturated to maximum, then the verification fails; Otherwise, it passes. Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass