G36ReturnAirDamperPositionForReliefDamperOrFan ==================================================================== Brief Description ------------------------------------------------------------------------------- Verify that the return air damper operation follows guideline 36 recommendations for systems with relief damper/fan Detailed Description ------------------------------------------------------------------------------- Verify that the return air damper operation follows the guideline 36 recommendations for supply air temperature setpoint operations Index Description ------------------------------------------------------------------------------- * Section 5.16.2.3 in ASHRAE Guideline 36-2021 Datapoints Description ------------------------------------------------------------------------------- * output_coil_heating: Heating output * output_coil_cooling: Cooling output * position_damper_air_return_max: Maximum return air damper position * position_damper_air_return: Return air damper position * position_damper_air_outdoor: Outdoor air damper position * position_damper_air_outdoor_max: Maximum outdoor air damper position Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass Assertions Description ------------------------------------------------------------------------------- * if output_coil_heating > 0 * if abs(position_damper_air_return - position_damper_air_return_max) < 0 * pass * else * fail * end * else if output_coil_cooling > 0 * if abs(position_damper_air_return) < 0 * pass * else * fail * end * else if pos_damper_oa < position_damper_air_outdoor_max * if abs(position_damper_air_return - position_damper_air_return_max) < 0 * pass * else * fail * end * else if abs(pos_damper_oa - position_damper_air_outdoor_max) < 0 * if position_damper_air_return < position_damper_air_return_max * pass * else * fail * end * end