G36ReliefAirDamperPositionForReturnFanAirflowTracking ==================================================================== Brief Description ------------------------------------------------------------------------------- Verify that the outdoor air damper operation follows guideline 36 recommendations for systems with return fan with airflow tracking Detailed Description ------------------------------------------------------------------------------- Verify that the outdoor air damper operation follows the guideline 36 recommendations for supply air temperature setpoint operations Index Description ------------------------------------------------------------------------------- * Section 5.16.2.3 in ASHRAE Guideline 36-2021 Datapoints Description ------------------------------------------------------------------------------- * output_coil_heating: AHU heating coil heat transfer rate * output_coil_cooling: AHU cooling coil heat transfer rate * position_damper_relief_max: Maximum relief air damper position * position_damper_relief: Relief air damper position * position_damper_air_return: Return air damper position Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass Assertions Description ------------------------------------------------------------------------------- * if output_coil_heating > 0 * if abs(position_damper_relief - 0) < 0 * pass * else * fail * end * else if output_coil_cooling > 0 * if abs(position_damper_relief - position_damper_relief) < 0 * pass * else * fail * end * else if abs(position_damper_relief - (1 - position_damper_air_return) * position_damper_relief) < 0 * pass * else * fail * end