G36ReheatTerminalBoxHeatingCoilLowerBound ==================================================================== Brief Description ------------------------------------------------------------------------------- Terminal box with reheat heating coil needs to keep discharge air temp no lower than 10c when occupied following the guideline 36 recommendations Index Description ------------------------------------------------------------------------------- * Section 5.6.5.4 in Guideline 36-2021 Datapoints Description ------------------------------------------------------------------------------- * mode_system: System operation mode * command_coil_heat: Heating coil command * temperature_air_discharge: Discharge air temperature Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass Assertions Description ------------------------------------------------------------------------------- * if mode_system != 'occupied': * untested * if mode_system == 'occupied': * if temperature_air_discharge < 10 and command_coil_heat < 99: * fail * else: * pass * end