ExteriorLightingControlOccupancySensingReduction ==================================================================== Brief Description ------------------------------------------------------------------------------- Exterior lighting control occupancy sensing reduction Datapoints Description ------------------------------------------------------------------------------- * number_occupants: Number of occupants * power_light_total: Total lighting power Assertions Description ------------------------------------------------------------------------------- * The algorithm verifies that the exterior lighting is controlled based on occupancy. It fails if the maximum reported total lighting power is greater than 1500 W and if the total mnaximum lighting power is not reduced by half when occupancy has not been detected for 15 mins. Otherwise, it passes. Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass